The setpoint adjusts the pause between two subsequent cranking cycles. 
NOTE:  
Learn more in the separate chapter Starting sequence.  
 
 
Setpoint: Crank attempts 
The setpoint adjusts the maximum number of cranking cycles. The alarm Start fail 
is issued when the engine does not start within this number of cranking cycles. 
NOTE:  
An gas engines the last cranking cycle is extended about 25% and the engine is 
cranked with closed gas valve during this additional time to ventilate the remaining 
gas.  
 
NOTE:  
Learn more in the separate chapter Starting sequence.  
 
 
Setpoint: Idle time 
This setpoint adjusts duration of the idle period, which begins in the moment when 
the engine is started (e.g. the starter motor is disengaged). The output 
Idle/Nominal is not active to keep the engine at idle speed (if the governor 
supports idling) during idle period. 
 
Setpoint: Min stab time 
This setpoint adjusts the minimum time between the end of the idle period and 
closing of the GCB. Closing of the GCB is blocked during this period even if