Active and Reactive Power control modes (MINT application only) 
System Base load 
Gen-set group is controlled on constant (or adjustable) power. The Baseload value can by changed by 
setpoint or via analog input. 
Important setpoints: ProcCtrlMulti: #SysLdCtrlPtM = BASELOAD; #SysBaseload; SysBaseLdMode. 
Local Baseload 
Selected gen-set from island or mains parallel running group can be loaded to constant LocalBaseload 
value. This engine is taken out from Load sharing and Power management. LocalBaseload value is reduced 
only when common group (actual) load is lower than this value. The gen-sets in the group will try to match 
their LocalBaseloads (when more than one) based on their controller addresses, so the first limited would be 
the one with the highest CAN address. I.e. this function will switch-off automatically in one or more 
controllers if there is not enough load to cover all the requested LocalBaseloads. 
Important setpoints: ProcCtrlMulti: LocalBaseload. 
System Base power factor 
Gen-set group is controlled in mains parallel to keep a constant (or adjustable) power factor. 
Important setpoints: ProcCtrlMulti: #SysPFCtrlPtM = BASEPF; #SysPwrFactor. 
Import-Export 
Gen-set group is controlled to keep constant (or adjustable) Import or Export value. The external controller 
InteliMains NT must be connected on the CAN2 to control gen-set group kW I/E. 
Important setpoints: ProcCtrlMulti: #SysLdCtrlPtM = LDSHARING. 
Import/Export power factor 
Gen-set group is controlled to keep constant (or adjustable) Import or Export power factor. 
Important setpoints: ProcCtrlMulti: #SysLdCtrlPtM = VSHARING. The external InteliMains NT controller 
must be connected on the CAN2 to control gen-set group PF I/E. 
Power management (MINT application only) 
Automatic gen-set start / stop function based on load changes and/or Running hours or Engine size. 
Following functions are available: 
Power management in kW 
Guarantees adjustable load reserve (load step) in kW. Suitable for load demand-based optimization. 
Activation: Pwr management:#Pwr mgmt mode = ABS (kW) 
Power management in kVA 
Guarantees adjustable load reserve (load step) in kVA. Suitable for generator- or busbar dimensioning-
based optimization. 
Activation: Pwr management:#Pwr mgmt mode = ABS (kVA)