IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
148
ALARM GROUPS ACCORDING TO BLOCKING TYPE
Setpoint: RunOnlyBlkDel2
Group
Engine protect
Range [units]
0.0 .. 3000.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay after engine start when the alarms configured as
RunOnlyBlkDel2 (i.e. "running only", group #2) are started to be evaluated. The
"running only" alarms are not beeing evaluated while the engine is not running or
then, after start, while the adjusted delay is running.
See the setpoint RunOnlyBlkDel1 for diagram of alarm groups and their blocking
periods.
Setpoint: RunOnlyBlkDel3
Group
Engine protect
Range [units]
0.0 .. 3000.0 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the delay after engine start when the alarms configured as
RunOnlyBlkDel3 (i.e. "running only", group #3) are started to be evaluated. The
"running only" alarms are not beeing evaluated while the engine is not running or
then, after start, while the adjusted delay is running.
See the setpoint RunOnlyBlkDel1 for diagram of alarm groups and their blocking
periods.

Table of Contents

Other manuals for ComAp IG-NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IG-NT and is the answer not in the manual?

ComAp IG-NT Specifications

General IconGeneral
BrandComAp
ModelIG-NT
CategoryController
LanguageEnglish

Related product manuals