IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
189
Setpoint: Phase window
Group
Sync/Load Ctrl
Range [units]
0 .. 90 [°]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts maximum absolute value of difference between actual phase
angle between the generator and mains/bus voltages for synchronizing.
NOTE:
To disable issuing the breaker close command (i.e. for test purpose) adjust this
setpoint to 0. Synchronizing will continue until timeout occurs or the breaker is
closed externally.
Setpoint: Dwell time
Group
Sync/Load Ctrl
Range [units]
0.0 .. 25.0 [s]
Related FW
3.0
Force value
possible
YES
Force value
possible
YES