ExtValue2LoLim .. 32000 [X]  
This setpoint adjusts the high limit of the value of ExtValue 2 if the value is 
lowered/raised by the binary inputs ExtValue2 up and ExtValue2 down. The 
ExtValue 2 is never raised over this limit. 
NOTE:  
This limit is not taken into account if the value ExtValue 2 is written remotely from 
a terminal using the appropriate command ExtValue #n.  
 
NOTE:  
For IS-NT only. 
 
 
Setpoint: ExtValue2 rate 
This setpoint adjusts the rate pre second at which the ExtValue 2 is beeing 
changed while the input ExtValue2 up or ExtValue2 down is active. 
 
Setpoint: ExtValue3deflt 
This setpoint adjusts the reset (initial) value of the ExtValue 3. This initial value is 
applied either when the controller is powered-on or when the ExtValue 3 is reset 
by the binary input ExtValue3reset. 
 
Setpoint: ExtValue3LoLim 
-32000 .. ExtValue3HiLim [X]  
This setpoint adjusts the low limit of the value of ExtValue 3 if the value is 
lowered/raised by the binary inputs ExtValue3 up and ExtValue3 down. The