IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
as the programming is allowed in OFF mode only and GenConfig is not able to 
switch the controller to OFF mode while AUT mode is forced by this input.  
 
Binary input: REMOTE: Remote TEST 
The controller is forced into TEST mode while this input is active. This input can 
be used, among others, for following purposes: 
  In combination with a timer module for periodic testing of the engine. 
  In combination with the input Test on load for forcing the genset to start 
and take over the load by one binary signal (manual switch, higher-level 
automation system etc.)  
 
Binary input: REMOTE: Remote off 
The controller is forced into OFF mode while this input is active and the genset is 
not running. The controller will return into the previous mode after the input is 
deactivated. If the genset is running, the mode does not change until it is stopped. 
Use this input if you need to disable the genset temporarily from any reason 
(maintenance, control from a higher-level automation system etc..). 
Binary input: REMOTE: Remote MAN 
The controller is forced into MAN mode while this input is active. 
NOTE:  
Programming of firmware and/or configuration is disabled while this input is active, 
as the programming is allowed in OFF mode only and GenConfig is not able to 
switch the controller to OFF mode while MAN mode is forced by this input.  
 
Binary input: REMOTE: Remote AUT/Remote SEM 
SEM mode is available in IS-NT only! 
The controller is forced into AUT or SEM mode while this input is active. 
NOTE:  
Programming of firmware and/or configuration is disabled while this input is active, 
as the programming is allowed in OFF mode only and GenConfig is not able to 
switch the controller to OFF mode while AUT mode is forced by this input.  
 
Binary input: REMOTE: Remote TEST 
The controller is forced into TEST mode while this input is active. This input can 
be used, among others, for following purposes: 
  In combination with a timer module for periodic testing of the engine. 
  In combination with the input Test on load for forcing the genset to start 
and take over the load by one binary signal (manual switch, higher-level