IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
 
Binary input: GCBButton 
This input is used for an external GCB button mounted on the switchboard. The 
function of the input is identical as function of the GCB button on the controller 
front panel. 
The input is enabled only if the setpoint Local Button is set to position 
EXTBUTTONS or BOTH. 
 
Binary input: MCBButton 
This input is used for an external MCB button mounted on the switchboard. The 
function of the input is identical as function of the MCB button on the controller 
front panel. 
The input is enabled only if the setpoint Local Button is set to position 
EXTBUTTONS or BOTH. 
 
Binary input: Load res 2 
This input is used to activate the load reserve set #2 instead of the set #1, which 
is active by default. The set #2 is adjusted by setpoints: 
  #LoadResStrt 2 and #LoadResStop 2 if the power management is 
switched to absolute mode  
  #%LdResStrt 2 and #%LdResStop 2 if the power management is 
switched to relative mode.  
CAUTION!  
All controllers cooperating together in Power management must have the same 
load reserve set selected. 
 
NOTE:  
It is possible to use virtual peripheries for distribution of the binary signal from one 
physical switch connected to one controller to all other controllers over the CAN 
bus.