IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
2.  Configure an universal protection block to the binary signal mentioned 
above and select protection type AL indication.  
3.  Configure the binary signal mentioned above onto the logical binary input 
IssueActCallC5.  
 
Binary input: AccessLock D#2 
This input forces the external local terminal or IntelliVision (display) #2 into 
monitoring mode. 
NOTE:  
Local display means that it is connected to dedicated RS485. There is possibility 
to connect up to 2 external displays in IG-NT-BB or 1 in IG-NT. It is possible to 
connect up to 3 external displays in IS-NT-BB and in IS-NT.  
 
  Setpoints changes are disabled. 
  Using control buttons on the panel is disabled even if the controller is in 
MAN mode. 
  Change of controller mode is disabled. 
 
Binary input: AccessLock D#3 
NOTE:  
For IS-NT and IS-NT-BB only. 
 
This input forces the external local terminal or IntelliVision (display) #3 into 
monitoring mode. 
NOTE:  
Local display means that it is connected to dedicated RS485. There is possibility 
to connect up to 2 external displays in IG-NT-BB or 1 in IG-NT. It is possible to 
connect up to 3 external displays in IS-NT-BB and in IS-NT.  
 
  Setpoints changes are disabled. 
  Using control buttons on the panel is disabled even if the controller is in 
MAN mode. 
  Change of controller mode is disabled. 
 
Binary input: NeutralCB fdb 
This input is used for connection of the normally open feedback contact from the 
Neutral contactor. If the input is active, the controller will consider the neutral 
contactor as closed and vice versa. See also description of the setpoint #Neutral 
cont.. 
 
Binary input: CylDifEvalBlk