IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
30
= 5s
Max stab time
ProtDel GroupX
Idle time
BO: Idle/Nominal
RPM
BO: Starter
Transition Idle - > Nominal RPM.
Starter switched off.
Underspeed protection
unblocked.
Electrical protections enabled.
„Engine running only“
protections of group X (=1 -3)
enabled.
Underspeed unblocking
Preventilation (if Fuel solenoid = GAS):
PreVentil time
BO: Fuel solenoid
RPM
BO: Starter
Last unsuccessful start attempt or
engine Shutdown.
Starter activated, but Fuel solenoid
delayed for PreVentil time because:
last start attempt wasn‘t successful or
engine Shutdown or
this is the first start attempt after the
controller switch -on.
Additional Fuel solenoid activation
delay can be caused by
FuelSol offset setting.
Ventilation (if Fuel solenoid = GAS ENGINE):
+25%
= MaxCrank time
BO: Fuel solenoid
RPM
BO: Starter
( CrankAttempts - 1) the attempt
The last crank attempt is extended by
25% of MaxCrank time, with Fuel
solenoid closed, to ventilate the gas
from the engine.
Fuel solenoid activation delay can
be set using FuelSol offset.

Table of Contents

Other manuals for ComAp IG-NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IG-NT and is the answer not in the manual?

ComAp IG-NT Specifications

General IconGeneral
BrandComAp
ModelIG-NT
CategoryController
LanguageEnglish

Related product manuals