IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
the chapter Power derating.
Analog input: PowerDerating2
This is the input into the Power derating block #2. See details about the function in
the chapter Power derating.
Analog input: LdCtrl:TByPwr
This functional input is used as the temperature input into the load control loop if
the loop is switched into "T BY PWR" position. More information is available at the
setpoint Load ctrl PtM.
Analog input: MLC:AnExSysBld
This functional input is used for requesting the system baseload externally by an
analog input. The setpoint SysBaseLdMode must be set to EXTERNAL to read
the system baseload from this input.
NOTE:
This logical analog input must be configured at each gen-set to the identical
source. The shared peripherial modules can be used to distribute the value over
the controllers via the CAN2 bus. See the note in the description of the setpoint
SysBaseLdMode.
Analog input: MPF:AnExSysBPF
This functional input is used for requesting the system power factor externally by
an analog input. The setpoint SysBasePFMode must be set to EXTERNAL to read
the requested system power factor from this input.
NOTE:
This logical analog input must be configured at each gen-set to the identical
source. The shared peripherial modules can be used to distribute the value over
the controllers via the CAN2 bus. See the note in the description of the setpoint
SysBaseLdMode.
Analog input: Cyl temp 1
Logical analog input for cylinder temperature #1. Used for computing of values T
Cyl aver, T Cyl max, T Cyl min.
NOTE:
Available in IS-NT only.