IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
133
Description
This setpoint adjusts the low limit of the value of ExtValue 1 if the value is
lowered/raised by the binary inputs ExtValue1 up and ExtValue1 down. The
ExtValue 1 is never lowered below this limit.
NOTE:
This limit is not taken into account if the value ExtValue 1 is written remotely from
a terminal using the appropriate command ExtValue #n.
NOTE:
For IS-NT only.
Setpoint: ExtValue1HiLim
Group
Force value
Range [units]
ExtValue1LoLim .. 32000 [X]
Related FW
3.0
Description
This setpoint adjusts the high limit of the value of ExtValue 1 if the value is
lowered/raised by the binary inputs ExtValue1 up and ExtValue1 down. The
ExtValue 1 is never raised over this limit.
NOTE:
This limit is not taken into account if the value ExtValue 1 is written remotely from
a terminal using the appropriate command ExtValue #n.
NOTE:
For IS-NT only.
Setpoint: ExtValue1 rate
Group
Force value
Range [units]
1 .. 10000 [X/s]
Related FW
3.0
Force value
possible
YES
Force value
possible
YES
Description
This setpoint adjusts the rate pre second at which the ExtValue 1 is beeing
changed while the input ExtValue1 up or ExtValue1 down is active.
Setpoint: ExtValue2deflt
Group
Force value
Range [units]
-32000 .. 32000 [x]
Related FW
3.0
Force value
possible
YES