IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
161
Group: Power management
Value: BankPriority
Group
Pwr management
Units
-
Related FW
3.0
Description
This value shows current priority number. It corresponds to the setpoint Priority
except following situations:
If at least one of binary inputs Priority SW "X" is configured on some
source and is active then the actual gen-set priority is given by the
combination of these inputs.
If a force value function is configured at the Priority setpoint and the
forcing binary input is active, the actual gen-set priority is given by the
alternative setting from the force value function.
If the Gen-set size optimalization is active then the actual priority is given
by the optimalization function.
Value: Act Reserve
Group
Pwr management
Units
-
Related FW
3.0
Description
Actual absolute reserve.
Value: Reserve
Group
Pwr management
Units
-
Related FW
3.0
Description
Actual absolute reserve for start. This value contains a copy of the setpoint
#LoadResStrt from the currently selected reserve set.
Value: Reserve Stp
Group
Pwr management
Units
kX
Related FW
3.0
Description
Actual absolute reserve - when the reserve is higher than this value the last
started gen-set (the gen-set with the highest priority) is stopped. This value
contains the following: #LoadResStop plus Nominal power of the genset which is
first to stop. #LoadResStop is used from the currently selected reserve set.
Value: ActRes rel
Group
Power management
Units
%