IGS-NT-BC, SW Version 1.2.0, ©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
193
bus. See the principial diagram of such distribution in the description of the input
Load res 2.
Binary input: Priority sw A
Related FW
3.0
Description
This is one of four inputs Priority sw A, Priority sw B, Priority sw C and Priority sw
D that can be used for selection of the power management priority externally.
These inputs are optional and if not configured, the priority is then adjusted by the
setpoint Priority.
ENCODING TABLE
PRIORITY
INPUT A
INPUT B
INPUT C
INPUT D
Default
0
0
0
0
1
1
0
0
0
2
0
1
0
0
3
1
1
0
0
4
0
0
1
0
5
1
0
1
0
6
0
1
1
0
7
1
1
1
0
8
0
0
0
1
9
1
0
0
1
10
0
1
0
1
11
1
1
0
1
12
0
0
1
1
13
1
0
1
1
14
0
1
1
1
15
1
1
1
1
NOTE:
"0" in the table means the input is not active or not configured.
NOTE:
"Default" is the priority adjusted by the setpoint Priority.
Binary input: Priority sw B
Related FW
3.0
Description
This is one of four inputs Priority sw A, Priority sw B, Priority sw C and Priority sw
D that can be used for selection of the power management priority externally.
These inputs are optional and if not configured, the priority is then adjusted by the