IGS-NT-BC, SW Version 1.2.0, ©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
Binary output: Horn flashing
This is the flashing alternative of the output Horn, i.e. the output flashes with
period 1s/1s while the output Horn is closed.
Binary output: FltResButnEcho
This output provides 1s pulse when:
• Fault reset button is pressed on the controller front panel or
• Fault reset button is pressed on any of external local/remote terminals or
• fault reset command is received via communication line or
• the input FaultResButton is activated.
Binary output: HrnResButnEcho
This output provides 1s pulse when:
• Horn reset button is pressed on the controller front panel or
• Horn reset button is pressed on any of external local/remote terminals or
• horn reset command is received via communication line or
• the input HornResButton is activated.
Binary output: StartButnEcho
This output provides 1s pulse when:
• Start button is pressed on the controller front panel or
• Start button is pressed on any of external local/remote terminals or
• start command is received via communication line or
• the input StartButton is activated.
Binary output: StopButnEcho
This output provides 1s pulse when:
• Stop button is pressed on the controller front panel or