IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
68
Setpoint: Derated1 pwr
Group
Process control
Range [units]
0 .. 100 [%]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the final power level for the Power derating 1
function. The nominal power is not reduced below this setpoint even if the
respective analog input increases further.
See the chapter Power derating for details.
Setpoint: Derating2 strt
Group
Process control
Range [units]
-32000 .. +32000 [x]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the starting point of the Power derating 2
function, where the gen-set nominal power is still 100% of the setpoint Nomin
power.
See the chapter Power derating for details.
NOTE:
The setpoint actual physical dimension depends on configuration of the physical
analog input to which the logical input PowerDerating2 is assigned.
Setpoint: Derating2 end
Group
Process control
Range [units]
-32000 .. +32000 [x]
Related FW
3.0
Force value
possible
YES
Description
This setpoint is used for adjusting the end point of the Power derating 2 function,
where the gen-set nominal power is reduced to the value adjusted by setpoint
Derated2 pwr.
See the chapter Power derating for details.
NOTE:
The setpoint actual physical dimension depends on configuration of the physical
analog input to which the logical input PowerDerating1 is assigned.