– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 36
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
Battery <Volts [V]
Warning threshold for low battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery >Volts)
Test Period [d]
After the given value of Test Period setpoint expires, the engine is started and is running as long as
the value of Test Duration setpoint. Test Period starts counting always when the engine is stopped.
Range: 0 – 240 days
^ Available only in AMF8, 9.
Test Duration [min]
Time interval, when engine is running after expiring the Test Period setpoint.
Range: 0 – 240 minutes
^ Available only in AMF8, 9.
Hint:
This function does not work till both setpoints (Test Period and Test Duration) are set to non-zero
values.
Hint:
The communication setting for both communication ports on IL-NT controller is presetted
subsequently:
For MRS3 and AMF8: COM1 Mode is DIRECT – direct/internet communication
COM2 Mode is DIRECT – direct/internet communication
For MRS4 and AMF9: COM1 Mode is DIRECT – direct/internet communication
COM2 Mode is ECU LINK – protocol for communication with Cummins
engines via Modbus
^AMF Settings
^ This group of setpoints is available only in AMF8, 9.
EmergStart Del [s]
Delay after the mains failure to the start of the gen-set
Step: 1s
Range: 0 – 600 s
Mains Ret Del [s]
Delay after the mains return to the GCB opening.
Step: 1s
Range: 1 – 3600 s
Mains >V [%]
Threshold for mains overvoltage. All three phases are checked. Maximum out of three is used.
Step: 1% of Nominal voltage
Range: 50 (Mains <V) – 150%