– MRS3,4, AMF8,9, SW version 1.4, ©ComAp – October 2008 35
IL-NT-MRS3,4-AMF8,9-1.4-Reference Guide.pdf
MaxCrank Time [s]
Maximum time limit of cranking.
Step: 1s
Range: 1 – 60 s
Cooling Time [s]
Runtime of the unloaded gen-set to cool the engine before stop.
Step: 1s
Range: 0 – 3600 s
Hint:
Cooling is executed at nominal speed and generator protections are active.
Al1 Wrn [ Bar]
Warning threshold level for ANALOG INPUT 1
Step: 0,1 bar
Range: -10 – 1000
Al1 Sd [ Bar]
Shutdown threshold level for ANALOG INPUT 1
Step: 0,1 bar
Range: -10 – 1000
Al1 Del [s]
Delay for ANALOG INPUT 1
Step: 1 s
Range: 0 – 900 s
Al2 Wrn [°C]
Warning threshold level for ANALOG INPUT 2
Step: 1 °C
Range: -100 – 10000
Al2 Sd [°C]
Shutdown threshold level for ANALOG INPUT 2
Step: 1 °C
Range: -100 – 10000
Al2 del [s]
Delay for ANALOG INPUT 2 alarm.
Step: 1 s
Range: 0 – 900 s