Communication Guide, ©ComAp March 2014 100
IGS-NT Communication Guide 03-2014.pdf
11. For each write-type parameter modify the property Update mode to triggered mode and define
trigger byte address. The Profibus master must update the parameter data field first and then
increase the trigger byte value to write the parameter (register) to the controller.
12. Write the configuration to the P485 and save it also to disk as backup.
Controller settings
IG/IS-NT
Comms settings: RS232(1) mode / RS232(2) mode* = MODBUS-DIRECT
Comms settings: RS232(1)MBCSpd / RS232(2)MBCSpd* = according to converter setting
Comms settings: RS485(1)conv. / RS485(2)conv.* = according the converter setting
* Second RS232/485 port available only in IG-NTC/EEC and IS-NT.
Anybus Comunicator - Modbus RTU to Profibus and other
communication standards converter
Anybus comunicator is converter from Modbus RTU (RS232, RS422, RS485) to Profibus and other
communication standards. See more information on manufacturer web page.
See deatils on the web page of the manufacturer:
http://www.hms.se/products/products.asp?PID=104&ProductType=Anybus%20Communicator
Download user manual and configuration manual
http://www.hms.se/upload/104-0855-ABC-PDP_2_53.pdf