Communication Guide, ©ComAp March 2014 122
IGS-NT Communication Guide 03-2014.pdf
Each user has his identification number (0 7). User with identification number 0 has an exceptional
position. This user has access to all groups of protected objects (this access cannot be changed
anyhow) and can define groups of access attributes to other users (1 7), reset their password and
set their name (alias of an identification number). Entering of password must be foregone by writing of
a user identification number.
Commands for IGS-NT
First it is necessary to enter an appropriate user and his password first to enable commands, if these
are protected by level 1-7
Command (*)
Meaning
Argument
(*)
Return value
(*)
1
Engine start
01FE0000
000001FF
OK
2
Argument has not been
written
Engine stop
02FD0000
000002FE
OK
2
Argument has not been
written
Horn reset
04FB0000
000004FC
OK
Fault reset
08F70000
000008F8
OK
ECU Fault reset
10EF0000
000010F0
OK
other
1
Wrong argument
2
Close/open generator circuit breaker (IGS-
NT)
Clutch ON/OFF (ID)
11EE0000
000011EF
OK
2
Argument has not been
written
Close generator circuit breaker
11EF0000
000011F0
OK
2
Argument has not been
written
Open generator circuit breaker
11F00000
000011F1
OK
2
Argument has not been
written
Close/open mains circuit breaker
12ED0000
000012EE
OK
2
Argument has not been
written
Close mains circuit breaker
12EE0000
000012EF
OK
2
Argument has not been
written
Open mains circuit breaker
12EF0000
000012F0
OK
2
Argument has not been
written
other
1
Wrong argument
5
Reset from Init state (#1)
44440000
00004445
OK
1
Not possible to perform
7
Statistics reset
007C0000
0000007D
OK
1
Not possible to perform
8
Set kWh counter
New value
N/A
C
Set kVAhr counter
New value
N/A
D
Set counter of engine starts
New value
N/A
E
Set runhours counter
New value
N/A
19
Set counter of unsuccessful engine starts
New value
N/A
1A
Set binary output RemoteSwitch1-8
(RemoteControl1-8 )
00200000
N/A
Reset binary output RemoteSwitch1-8
(RemoteControl1-8 )
00100000
N/A
1F,20,21,22
Set pulse counters (IS-NT only)
XXXXYYYY
(XXXX
Upper value +
1
OK