Communication Guide, ©ComAp March 2014 123
IGS-NT Communication Guide 03-2014.pdf
Upper part
of a new
value;
YYYY
Lower part
of a new
value)
1, 2
Not possible to perform
23,24,25,26
Set ExtValue1-4 (#2)
0002YYYY
(YYYY -
new value)
3
OK
1, 2
Not possible to perform
(*) in HEX
# 8
If the controller setpoints are not valid after it is switched on, the controller goes to a blocked state. In
this state it is necessary to modify the setpoints from the controller keypad and switch off and on the
controller or from the external terminal and unblock the controller by Reset from Init state command.
Another condition necessary to unblock the application function of the controller is valid configuration.
# 2
Check if the setpoints ExtValueXLoLim and ExtValueXHiLim allow set the requested value to
ExtValue.
Commands for IM-NT
First it is necessary to enter an appropriate user and his password first to enable commands, if these
are protected by level 1-7
Command
Meaning
Argument (*)
Return value
(*)
1
Start command
01FE0000
000001FF
OK
2
Argument has not been
written
Stop command
02FD0000
000002FE
OK
2
Argument has not been
written
Horn reset
04FB0000
000004FC
OK
Fault reset
08F70000
000008F8
OK
other
1
Wrong argument
2
Close/open MGCB
11EE0000
000011EF
OK
2
Argument has not been
written
Close MGCB
11EF0000
000011F0
OK
2
Argument has not been
written
Open MGCB
11F00000
000011F1
OK
2
Argument has not been
written
Close/open MCB / BTB
12ED0000
000012EE
OK
2
Argument has not been
written
Close MCB / BTB
12EE0000
000012EF
OK
2
Argument has not been
written
Open MCB / BTB
12EF0000
000012F0
OK
2
Argument has not been
written
other
1
Wrong argument
5
Reset from Init state (#1)
44440000
00004445
OK
1
Not possible to perform
8
Set kWh counter
New value
N/A
C
Set kVAhr counter
New value
N/A
1A
Set binary output RemoteSwitch1-8
(RemoteControl1-8 )
00200000
N/A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NTC and is the answer not in the manual?

ComAp InteliGen NTC Specifications

General IconGeneral
BrandComAp
ModelInteliGen NTC
CategoryController
LanguageEnglish

Related product manuals