IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
126
Description
This setpoint adjusts the rate of increasing of the PulseCounter #3 module. The
module counts pulses at the input PulseCounter 3 and if the input pulses counter
reaches value given by this setpoint, the counter value PulseCounter 3 (in the
group Statistic) is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Setpoint: ConvCoefPulse4
Group
Basic settings
Range [units]
1 .. 6500 [-]
Related FW
3.0
Description
This setpoint adjusts the rate of increasing of the PulseCounter #4 module. The
module counts pulses at the input PulseCounter 4 and if the input pulses counter
reaches value given by this setpoint, the counter value PulseCounter 4 (in the
group Statistic) is increased by 1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Group: Comms settings
Setpoint: Gen-set name
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
This setpoint is intended for a custom name of the gen-set, which is used for
identification of the gen-set in saved archives or remote connections. Maximal
length of the name is 15 characters.
The setpoint can't be modified via the IG-NT built-in terminal.
Setpoint: Contr. address
Group
Comms settings
Range [units]
1 .. 32 [-]
Related FW
3.0
Description
This setpoint adjusts the address of the particular controller at the CAN2 and/or
RS485 bus. Each gen-set connected to the same bus must have unique
address.
If the setpoint CANnegotiation (COMBI application only) is in AUT position, the
address is assigned automatically. The setpoint Contr. addr is preffered then,
however if it is in conflict with other controller present on the CAN2 bus other
address will be assigned to aviod address collision.
NOTE:
Address 1 is reccommended for standalone gen-sets.
NOTE:
If you are connecting to the gen-set remotely you have to adjust the proper
controller address in connection settings of the remote client (InteliMonitor,

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals