IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
The setpoint selects function of the terminal address 122 at the CAN2 line. See
the latest communication guide for details about this topic.
The address is used for modem connection via I-LB
The address is used for direct connection to any other device as
e.g. IV8 or I-RD.
Setpoint: CANAddrSwitch2
The setpoint selects function of the terminal address 125 at the CAN2 line. See
the latest communication guide for details about this topic.
The address is used for modem connection via I-LB
The address is used for direct connection to any other device as
e.g. IV8 or I-RD
Setpoint: CANnegotiation
This setpoint defines if CAN address is used in the standard way or CAN
addresses are reconfigured internally.
The control unit has the same address which is necessary for
communication. The address can be changed only from InteliMonitor
or controller screen.
Controllers can change their addresses when are interconnected via
CAN2 bus to prevent CAN bus collision. Controller address is set up
to different address if another unit with the same address is detected
on the CAN bus.
CAUTION!
Make sure all controllers have this setpoint set to AUT. It does not
work properly if there are controllers with this setpoint adjusted to
OFF and others with AUT setting.
CAUTION!
This function is not designed to cooperate with controllers which do
not support it. Make sure it is adjusted to OFF if there are other
controllers on the CAN without this setpoint.
Setpoint: IP address