IGS-NT Combi, SW Version 3.0, ©ComAp – May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
134
Description
ï‚· In fixed settings mode this setpoint is used to adjust the network mask of
the network segment where the controller is connected.
ï‚· In Automatic settings mode this setpoint is used to display the network
mask which has been assigned by the DHCP server. It is not possible to
change the setpoint value manually in this setting (the value is
immediately reverted back by controller communication module IB-COM).
Setpoint: Gateway IP
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
ï‚· In fixed settings mode this setpoint is used to adjust the IP address of the
gateway of the network segment where the controller is connected.
ï‚· In Automatic settings mode this setpoint is used to display the gateway IP
address which has been assigned by the DHCP server. It is not possible
to change the setpoint value manually in this setting (the value is
immediately reverted back by controller communication module IB-COM).
A gateway is a device which connects the respective segment with the other
segments and/or Internet.
Setpoint: ComApProtoPort
Group
Comms settings
Range [units]
1 .. 255 [-]
Related FW
3.0
Description
This setpoint is used to adjust the port, which is used for ethernet connection to a
PC with any of ComAp PC program (i.e. InteliMonitor, GenConfig). This setpoint
should be adjusted to 23, which is the default port used by all ComAp PC
programs. A different value should be used only in special situations as e.g.
sharing one public IP address among many controllers or to overcome a firewall
restrictions.
Setpoint: AirGate
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Description
This setpoint selects the ethernet connection mode.
DISABLED
This is a standard mode, in which the controller listens to the
incoming traffic and answers the TCP/IP queries addressed to
him. This mode requires the controller to be accessible from
the remote device (PC), i.e. it must be accessible at a public
and static IP address if you want to connect to it from the

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals