Atena Easy Addressable Fire Alarm Panel – Installation and Programming Manual
34
41PAM000 – Manual call point for indoor mounting
41PAE020 – Manual call point for outdoor mounting IP67
Use the functional buttons to set the following specialized parameters:
(3) EVENT EVACUATION/ ALARM – Every pressing of the button alternatively changes the type of the event
generated with activation of the manual call point:
- Event EVACUATION – The sounders will be activated immediately, as the set time delays Т1 and Т2 are
ignored.
- Event ALARM – The set time delays Т1 and Т2 are active and the manual call point operated as an
automatic detector.
41SAI000 – Wall mounted sounder with isolator
Use the functional buttons to set the following specialized parameters:
(1) SND LEVEL – Every pressing of the button alternatively changes the sound level between HIGH/ LOW – as this
depends on the number of the connected sounders to the loop:
- HIGH – Set in those cases when the number of the connected sounders* to the loop is up to 30.
- LOW – Set in those cases when the number of the connected sounders* to the loop is up to 60.
* Sounders 41SAI000, 41SCI000
(4) ON/ OFF TURN – Press to switch on/ off the sound of the sounder when checking for double addresses or finding
the place of installation.
41SCI000 – Wall mounted sounder and strobe with isolator
Use the functional buttons to set the following specialized parameters:
(1) SND LEVEL – Every pressing of the button alternatively changes the sound level between HIGH/ LOW – as this
depends on the number of the connected sounders to the loop:
- HIGH – Set in those cases when the number of the connected sounders* to the loop is up to 30.
- LOW – Set in those cases when the number of the connected sounders* to the loop is up to 60.
* Sounders 41SAI000, 41SCI000.
(3) MODE – Press to choose the operation mode of the sounder:
SND – Sounder activation only in FIRE mode;
FLASH – Flash indication only in FIRE mode;
SND/ FLASH – Both sounder and flash indication are active in FIRE mode.
(4) ON/ OFF TURN – Press to switch on/ off the sound and LED indication of the sounder when checking for double
addresses or finding the place of installation.