212-M-V2.1
Set-up Mode 43
Parameter Value Description
4. UNITS SI
US
Metric units.
US units.
5. ENERGY Set energy units for display.
6. VOLUM Set volume units for display.
7. POWER Set power units for display.
8. FLOW Set flow rate units for display.
9. FACTOR xxx.x p/ltr The K-factor of the flowmeter which
has been programmed.
(See flowmeter manufacturer's data.)
10. CUTOFF x.xx Hz Low frequency cut-off of the flowmeter,
expressed in Hz. The Model 212 will not
register flow if the input frequency is
below this value. Note that the default is
0.25Hz and it is recommended to not
change this value unless the flowmeter
produces very low frequencies.
(See Section 3.4.)
11. OFFSET x.x
YES
0.0
NO
The offset between temperature
sensors.
(See Section 3.5).
The offset function is disabled.
12. FM LOC Feed
Ret
Location of the flowmeter as being
in either the feed or return line.