Service manual OEB/OES/OGB/OGS
Page 3 / 6
Service no.:
Description
Plug
Pin
OES 6.06
OEB
OES
OGB
OGS
Minimum
settin
Maximum
settin
Default value
Comments
Unit
r29 Software OM
r30 Software CM
r31 Software GM
r32 not used
r33 not used
r34 not used
r35 not used
r36 not used
r37 not used
r38 Error (last error message)
Using the scroll button
call up the last 10 errors
r39 Appliance no.
r40 Article no.
c01 SG Pre-heating temperature
50 95 88 °C
c02 Condenser temperature
50 95 68 °C
c03 On time fan motor cycle
1 20 2 s
c04 Off time fan motor cycle
0 90 60 s
c04
Time steaming with REG
0 99 4
Min
ute
c05 Permanent steaming
0 1 0
00 = regulated
01 = permanent
steaming
c06 New init (hard reset)
0 1 0
01 = all modules (OM,
CM, CommM) are re-
initialised
c07 Moisture S (Steaming)
50 95 87 °C
c07 Moisture Steaming
0 99 25 sec
Time solenoid valve on
Higher is damper
c08 Moisture SS (Superheated
Steam)
50 96 90 °C
c08 Moisture HLD + REG
0 99 12 sec
Time solenoid valve on
Higher is damper
c09 Moisture Quick
50 96 90 °C
c09 Moisture Steaming Quick
0 99 12 sec
Time solenoid valve on
Higher is damper
c10 Moisture Reg
5 20 12 °C
C10 Solenoid valve off in all
cooking programmes
0 99 40 sec
Time solenoid valve off
Higher is drier
c11 Scaling level
0 25 20 °C
Temperature difference
between B8 and B4
C11 Vapour reduction
0 25 0 sec
Time solenoid valve
off, switched on fixed 3
secs.
c12 Bit field 1
- - -
Activate options: 300
Deactivate options: 305
c13 Bit field 2
- - -
Options: CTS = 001
Autom. cleaner = 024
Dummy vers. = 999
AS/11-2011 3_01e Customer service - Service programme_f