ASCII I/F
CoolMasterNet PRM Rev 0.7
31
www.coolautomation.com
© 2017 CoolAutomation
response will be illegal data address.
EXAMPLE
List current ModBus configuration
>modbus
ModBus IP : disabled
server port : 502
CG4 ignore : none
OK
Enable ignore setting
>modbus ignore r
OK
Lisk current ModBus configuration
>modbus
ModBus IP : disabled
server port : 502
CG4 ignore : regs
OK
Disable ignore setting
>modbus ignore r
OK
Enable ModBus IP
>modbus IP enable
OK, Boot Required!
Change ModBus IP server port
>modbus server port 500
OK, Boot Required!
List CoolGate 4 ModBus addresses of existing Indoor Units
>modbus cg4
L1.100 --> Hex: 0x1001, Dec: 4097
L1.101 --> Hex: 0x1011, Dec: 4113
OK
6.2.2 HVAC Status and Control Commands
on
allon
off
alloff
cool
heat
fan
dry
auto
haux
temp
fspeed
swing
filt
stat
ls
ls2
query
feed