24
COOLIUS A10
If the couplers are not joint to the stand or the coupler valves are not closed, Message:
9. Press START key to conrm.
The machine starts. The process cleans the complete
unit included the service hoses.
At the end,
10. Press STOP key at the end.
The machine is ready.
Join HP/LP couplers
to the stand and
close the valves!
Confirm by “START“
Internal flushing
end.
5.2 Fast service
1. Turn COOLIUS SELECT to select FAST SERVICE.
Press ENTER to conrm.
2. Turn COOLIUS SELECT to select the programs avail-
able:
RECOVERY
VACUUM / A/C SYSTEM CHARGE
3. Press ENTER to conrm.
Recovery
1. Turn COOLIUS SELECT to set the value.
Minimum: 2 min.
Maximum: 12 min.
2. Press ENTER to conrm.
The equipment performs the process.
Recovery, residual refrigerant check, used oil drain
process.
Vacuum / A/C system charge
1. Turn COOLIUS SELECT to set the vacuum time.
Minimum: 0 min.
Maximum: 999 min.
2. Press ENTER to conrm.
3. Turn COOLIUS SELECT to set the leak test time.
Minimum: 2 min.
Maximum: 60 min.
4. Press ENTER to conrm.
Fast Service

Recovery
Residual refrigerant
check.
min. 2
Vacuum time
min. 15
Leak test min. _