Appendix
Section 8
Access control passwords
Access to various menus is controlled by passwords, this is to prevent unauthorised access to
menus which could result in system malfunction or the deletion / corruption of site configuration
data.
Access to levels 2 and 3 should only be available to suitably trained and competent personnel, it
is strongly recommended that this password information stored in a secure location all activity
carried out at the panel is stored in the event log which can only be reset by Cooper Lighting and
safety personnel.
Level 2 password
Level 3 password
The password to access level 2 is 2214.
The password to access level 3 is 143243.
KEY POINTS
l
l
l
l
l
l
l
Never carry out insulation tests on cables connected to electronic equipment.
DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS.
Always use the correct type of cables as defined in the current Easicheck installation
planning guide.
Always adhere to volt drop limitation when sizing cables.
Always observe polarity throughout. Non colour coded conductors should be
permanently identified.
The Panel utilises intelligent soft addressing technology to greatly simplify the
installation and commissioning processes. Once the system has been installed and the
autolearn menu selected, the control panel will automatically scan the data loop and
allocate each device with an address number corresponding with its position on the
loop, this avoids the traditional need for manual addressing of the system devices which
is time consuming and provides a potential for error.
It is of vital importance that accurate details are kept of the exact wiring route in order to
determine which address has been allocated to each device.