ENG
29
Service settings manual J5060403 v1.2
Basic settings :
Parameter
Function Parameter description Setting range
Default
value
P1.1
AUT. SWITCHOVER
SUMMER/WINTER
Automatic switch-off of heating in accordance to average
one-day outdoor temperature.
0- NO
1- YES
0
P1.2
AVERAGE OUTDOOR
TEMP. FOR SUMMER/
WINTER SWITCHOVER
Setting of average one-day outdoor temperature at which
the heating should switch-off. 10 ÷ 30 °C
18
P1.4
REQUESTED ROOM
TEMPERAT. BY FROST
PROTECTION
Setting of room temperature when heating is switched off.
2 ÷ 12
6
P1.5
TEMPERATURE ROUND
UP
You set the accuracy of displayed temperatures.
0- 0.1 °C
1- 0.2 °C
2- 0.5 °C
3- 1 °C
2
P1.6
AUT. SHIFT OF CLOCK
TO SUMMER/WINTER
TIME
With the help of a calendar, the controller carries out the
automatic changeover between summer and winter time.
0- NO
1- YES
1
P1.7
PERIOD OF TEMPERAT.
LOGGING (MINUTES)
By setting this field you define how often the measured
temperatures are saved.
1 ÷ 30 min
5
P1.8
TONES
By setting this field you define sound signals of the con-
troller.
0- OFF
1- KEYPAD
1
P1.9 ADVANCED
TEMPERATURE SCREEN
Advanced screen means that while checking temperatu-
res you can see measured and required or calculated
temperature.
0- NO
1- YES
1
P1.10 LEVEL OF PROTECTION
AGAINST FROST
With this setting, we determine the level of protection
against frost that depends on the assessment of the
possibilities for frost on the facility.
Choose 0 level, when there is no possibility of frost on the
facility.
Choose 1 level, when there is a possibility of frost on the
facility. If room temperature sensor isn't connected,
heating system parts that are particularly exposed to
freezing are protected, when heating is switched off.
Choose 2 level, when there is a possibility of frost on the
facility. Heating system parts that are particularly exposed
to freezing are protected, when heating is switched off.
Choose level 3, when the possibility of frost on the facility
is considerable and parts of the heating system are
particularly exposed to freezing.
0 – NO PRO-
TECTION
1 - LEVEL 1
2 - LEVEL 2
3 - LEVEL 3
(GREATEST
PROTECTION)
1