Thermostats Crestron CHV-TSTAT and CHV-THSTAT
Slab 3 – Single Stage Heat with Slab
Minimum/Maximum
Press and hold the MODE and VIEW buttons simultaneously for five seconds to
enter setup mode.
SYSTEM SETUP
SETUP: SYSTEM
Heat Sys Type:
Slab MAX T:
Slab Reg:
SLAB 3
122
o
6
1 STG SPACE HEAT BY SLAB
WITH SLAB MIN/MAX (W1)
Heat System Type: SLAB 3
Slab Maximum Temperature: 39 to 122° F
(39 – 50° C). Used to prevent the floor from
becoming too hot on long heat calls.
Slab Regulation:
1 = Narrow temperature regulation
6 = Wide temperature regulation
NOTE: Slab mode 3 requires a slab remote
sensor and an air temperature sensor.
SYSTEM PERFORMANCE
SETUP: SYSTEM PERF
Heat Anticipator:
5
Heat Anticipator:
(valid selections are 1 through 6)
Low number = more frequent cycles and faster
response (tighter regulation).
High number = less frequent cycles and slower
response (looser regulation).
HUMIDIFIER OPTIONS
SETUP: HUM OPTS
Show Hum Mode Pg:
Show Hum View Pg:
Cold Weather Comp:
Y
Y
N
SYSTEM ENABLE/DISABLE
PAGE
Show Hum Mode Pg and Show Hum View
Pg: Select Y to show humidity page in normal
operation.
Cold Weather Compensation: Modifies the
humidifier output to prevent condensation on
the windows. Requires an outdoor temperature
source (CHV-THSAT, or CHV-TSTAT with
CHV-RTHS, CHV-RTS, or CHV-RSS).
Continued on the following page.