22
Released on 10/31/05 - X800058A UV Pure Technologies Inc. © 2005
No part of this document may be photocopied, reproduced, transmitted, or translated to another language without the
prior written consent of UV Pure Technologies Inc.
For additional info call 1-888-407-9997 or email info@uvpure.com
or visit www.uvpure.com
Step 8: Now that the disinfection procedure is complete you will need to return
the filter to its housing. Shut off the water supply, relieve water pressure by
opening a faucet, and return the filter to the housing. Allow a few days after a
disinfection procedure before getting a sample since residual chlorine may affect
the results.
Have the water tested by a local recognized testing agency prior to any water
consumption. UV Pure partners with water testing organizations in select
locations throughout North America. Contact UV Pure for potential water testing
partners: 1-888-407-9997. The testing should be performed on a regular basis as
required by local regulations.
4.
MAINTENANCE
The Hallett will run unattended until a fault arises. If a fault does occur, the
solenoid valve will close, preventing water from flowing. The green light will go
out, one of the red lights will illuminate, and the alarm will beep. The fault must
be corrected to return the unit to normal operation and have the water flow again.
In addition to system faults, there are system warnings. System warnings do not
close the solenoid valve. A warning allows the problem to be addressed before
the solenoid valve closes. If the warnings are left unattended, a system fault will
occur. The alarm will sound when a warning arises, but it can be silenced for 24
hours by pushing and holding the Reset button for one second. The “Lamp” red
light will flash during a warning.
The disinfection of water will occur as long as the unit is properly maintained in
accordance with the instructions set out in this manual. Operating a
malfunctioning unit or defeating any system sensors may jeopardize the safety of
the water. If any system failure occurs and water enters the plumbing system
without being disinfected, if the valve has been placed into manual mode, or if
the optional bypass is used, any water used for drinking should be boiled. Under
these circumstances, the water supply should be disinfected after returning the
unit to normal operation.