particular user code will work. Addresses P151E - P200E are used to map the user code to the required Time
Zones. The actual Time Zone parameters are defined at addresses P791E - P814E.
More than one time zone can be assigned to a code. The time zones are numbered 1-8 and are selected by the
numeric buttons 1-8 on the keypad. A value of zero (0) entered at any of these addresses is fixed as 24 hour seven
day access and is the default time zone for all 50 user codes.
P151E TZ E Where TZ represents any Time Zone from 1-8 valid for User Code #1
P200E TZ E Where TZ represents any Time Zone from 1-8 valid for User Code #50
NOTE: The ability to assign more than one Time Zone to each user allows for different time based controls
for different days of the week.
INSTALLER CODE - P249E
This code is used to enter full Installer Program mode (Program light flashing) from Client Program mode (Program
light steady) The default installer code is 000000. To change this code you Must first be in Installer Program Mode
then enter your new installer code at address P249E. The new code will be flashed back to you automatically. The
Installer Code may vary from 3-6 digits in length.
If the alarm is Disarmed then the Installer Code can gain access directly to Installer Program Mode provided Option 6
at address P310E is on.
DURESS DIGIT - P350E
P350E 0-9 Duress Digit (Default 0) - A Duress Alarm is activated only when the "Duress Digit" defined at
this address is prefixed to a valid user code. The resulting Duress Alarm will disarm the Area in
the normal way, operate an output if one is defined and report a duress event via the dialler if
programmed to do so. Values of 0-9 may be entered at this address where 0 = option disabled
and 1-9 represent a valid Duress digit from 1-9.
OUTPUT PROGRAM OPTIONS
PRIMARY OUTPUT OPTIONS - P201E-P208E
This block of addresses (P201E - P208E) is used to map output modifiers to each of the 8 outputs available on the
Elite. The optional 4 way relay output board (OUTPUTX4) can be configured to follow the program options for any of
the 8 outputs, the 4 relays can be assigned as output 1 or 5, 2 or 6, 3 or 7 & 4 or 8.
P201E 1E = Invert output #1 - Default off
2E = Flash output #1 - Default off
3E = Single pulse to output #1 - Default off
4E = Lockout output #1 once reset - Default off
5E = Output mapped to Remote Command Control - Default off
6E = Output mapped to local Command Control - Default off
7E = Day zones linked to pulse timer - Default off
8E = Output pulses on a 24 hour zone alarm - Default off
Option 1 Invert Output - This option is used to invert the normal state of the output. The Elite uses open
collector type transistor switches and the default state of all outputs is off or high. When in alarm the
transistor switch is turned on and the output is switched low. The invert option reverses this function.
Option 2 Flash Output - This option causes the output to switch on and off at a rate set by the pulse timer for the
output when in alarm and is normally used to flash a lamp during an activation.
Option 3 Single Pulse to Output - This option, when applied, produces a single pulse set by the pulse timer at
the output during an alarm.
Option 4 Lockout Once Reset - This option is used to limit the output to one operation per arming period.
Option 5 Output mapped to Remote Command Control - This option is used to map an output to the remote
command control function whereby the output can be controlled via the telephone (this requires the
optional VOICE or DTMF board to be fitted)