PROGRAMMING AREA “A,B & C” PARAMETERS
AREA "A" PRIMARY OUTPUT OPTIONS - P281E - P288E
AREA "B" PRIMARY OUTPUT OPTIONS - P381E - P388E
AREA "C" PRIMARY OUTPUT OPTIONS - P481E - P488E
The addresses above allow a number Area based options to be assigned to any of the 8 outputs. Address P281
relates to Output 1 options for Area A, address P381 relates to Output 1 options for Area B and address P481
relates to Output 1 options for Area C.
P281E 1E = Normal zone alarms to output #1
2E = Stay Mode alarms to output #1
3E = Pendant chirps to output #1
4E = All zones sealed indication to output #1
5E = 2 second pulse on arming or disarming to output #1
6E = Spare
7E = Day zone alarms to output #1
8E = Spare
Option 1 Normal zone alarms to output #1 - This option will map alarms from normal zone alarms from Area "A"
to output #1. Normal zones are those which will only activate when the area is armed.
Option 2 Stay Mode alarms to output #1 - This option will map alarms from zones defined as Area "A" Stay
Mode to output #1. Zones are defined as being in Stay Mode at P445E and P465E
Option 3 Pendant Chirps to output #1 - This option will map two short pulses (Chirps) to output #1 when Area
"A" is armed via a radio key (Pendant) and four short pulses to output #1 when Area "A" is disarmed by
a radio key. The length of the pulses (Chirps) are set by the pulse timer for this output.
Option 4 All zones sealed indication to output #1 - This option will map an Area "A" “Ready” indication to
output #1. A “Ready” indication is produced when all zones in an area are sealed, i.e. zone lights off.
Option 5 2 second pulse to output #1 on arming or disarming - This option will map a 2 second pulse to
Output #1 each time Area "A" is armed or disarmed as defined at P302E options 6&7.
Option 6 Spare
Option 7 Day zone alarms (Chime) to output #1 - The option will map alarms from Area "A" zones defined as
Day Zones to output #1. Zones are defined as Day Zones at P453/454E and P473/474E. Day zones
are those which operate only during periods when the Area is disarmed and are normally used as door
bells and shop minders etc.
Option 8 Spare
Note: P282E through P288E are as above but apply to outputs 2-8 for Area A
Note: P382E through P388E are as above but apply to outputs 2-8 for Area B
Note: P482E through P488E are as above but apply to outputs 2-8 for Area C
AREA "A" SECONDARY OUTPUT OPTIONS - P291E - P298E
AREA "B" SECONDARY OUTPUT OPTIONS - P391E - P398E
AREA "C" SECONDARY OUTPUT OPTIONS - P491E - P498E
The addresses above allow a number of secondary Area based options to be assigned to any of the 8 outputs.
Address P291 relates to Output 1 options for Area A, address P391 relates to Output 1 options for Area B and
address P491 relates to Output 1 options for Area C.
P291E 1E = Any Bypass to output #1
2E = Auto-Bypass warning to output #1
3E = Entry beeps to output #1
4E = Exit beeps to output #1
5E = Control function to output #1
6E = Arm indication to output #1
7E = Stay Mode Arm indication to output #1
8E = Disarm indication to output #1