Page 32
P451E 1-8E Zone is 24 Hour Fire Zone - Where options 1-8 represent zones 1-8. 24 hour Fire zones will
activate whether the panel or area is armed or disarmed. If an entry delay is also assigned to a
24 hr Fire zone, the alarm will not trigger unless the zone is in alarm longer than the delay time
programmed. A Fire Zone will cause the output to pulse to differentiate it from a burglar alarm.
(Default none)
P452E 1-8E Zone is 24 Hour Auto-Reset - Where options 1-8 represent zones 1-8. 24 hour Auto-Reset
zones will activate whether the panel or area is armed or disarmed. If an entry delay is also
assigned to a 24 hr Auto-Reset zone, the alarm will not trigger unless the zone is in alarm longer
than the delay time programmed. An Auto-reset zone will seal automatically when the zone input
is restored back to normal i.e. does not require a code to reset an alarm. (Default none)
P453E 1-8E Day Zones - Where options 1-8 represent zones 1-8. Day zones are active during periods where
the panel or areas are disarmed and revert to normal zones during armed periods (Default none)
P454E 1-8E Continuous Day Zone - Where options 1-8 represent zones 1-8. The zone acts as a day zone at
all times (Armed and Disarmed) and will operate day alarms but not normal zone alarms (Default
none)
P455E 1-8E Siren Lockout Zones - Where options 1-8 represent zones 1-8. Zones with siren lockout
designation will only cause their assigned output/s to operate once per armed period. Led on =
zone locked out. (Default none)
P456E 1-8E Access Control door position input - Where options 1-8 represent zones 1-8. The door position
input becomes a 24 hour alarm zone and will alarm if the “Control” door is forced open or left open
too long. It will also automatically re-lock the door after the “Control” operation has occurred and
the door has been opened then closed again. (Default none)
P457E 1-8E Access Control Request to exit input - Where options 1-8 represent zones 1-8. The Request to
Exit input will operate the “Control” door output to release the door and start the Door open Too
long Timer. (Default none)
P458E 1-8E Zone will report multiple activations via dialler- Default 1-8. If this option is turned off then the
relevant zone will only report one alarm to a monitoring company during any single armed period.
If it is turned on, the zone can send multiple reports if activated more than once during a single
armed period.
P459E 1-8E Zone will be Monitored for Inactivity - Default none. A Zone with this option turned on will be
checked to ensure that it is triggered on a regular basis. If the zone is not triggered within the time
period set at P569E then an alarm will be generated as the detector may have become faulty or
could be masked. The timer period as set at address P569E is only active during the disarmed
period. If the timer has started due to inactivity of a zone input, the elapsed time is remembered at
the time of arming and will resume when the alarm is disarmed.
P460E 1-8E Can Arm if Zone is Unsealed - Default None. If a zone is unsealed (Not Ready) at the time of
arming, by default the panel will Arm and the zone will be automatically bypassed at the end of
the exit delay. If option #1 at P301,P401 or P501 is on then the panel will not Arm if a zone in that
area is unsealed. If this option is set for any zone then the panel will ignore an unsealed condition
on the selected zone/s and allow arming to happen.
HIGH ZONE PROGRAM OPTIONS (9-16) - P461E - P480E
Combinations of options in addresses P461E to P480E may be used to give the most suitable zone behaviour.
P461E 1-8E Zone is in Area "A" - Where options 1-8 represent zones 9-16 respectively. This option assigns
a zone to Area "A" within a partitioned system. If the system is not partitioned, all zones must be
assigned to Area "A". (Default all in Area "A") See P310E8E also.
P462E 1-8E Zone is in Area "B" - Where options 1-8 represent zones 9-16 respectively. This option assigns
a zone to Area "B" within a partitioned system. (Default none in Area "B") See P310E8E also.
If a zone is defined in both Area "A" and Area "B" it is deemed to be in Area "C"
P463E 1-8E Zone is a normally open input - where options 1-8 represent zones 9-16 respectively. This