Page 33
option is used when normally open detectors such as smoke detectors are to be connected to a
zone. The option only applies if zone doubling is turned On at P410E. Default is all zones
normally closed.
P464E 1-8E Zone is a radio detector - Where options 1-8 represent zones 9-16 respectively. This option is
used when Radio (wireless) devices are used as detectors. (Default none)
P465E 1-8E Stay Mode Zones - Where options 1-8 represent zones 9-16 respectively. Zones included at this
address will become active when the panel is in Stay Mode. Zones not assigned at this address
will be excluded. (Default 1-4) Note: Stay Mode Zones are linked to Area assignments.
P466E 1-8E Zone can be Bypassed - Where options 1-8 represent zones 9-16 respectively. This option
determines if a zone can be Bypassed either manually or via the Auto-Bypass process. (Default
all on)
P467E 1-8E Auto Bypass Zones - Where options 1-8 represent zones 9-16 respectively. Zones assigned
Auto Bypass function at this address will be automatically bypassed by the system if they are
unsealed when the exit timers expire. Zones not given Auto Bypass status will cause an
activation if they are unsealed at the end of the exit delay period. (Default all on)
P468E 1-8E Zone is a handover - Where options 1-8 represent zones 9-16 respectively. Zones defined at
this address as handover are given the unique ability to behave as both delay and instant zones.
If a zone defined as an entry delay zone has been activated and the entry delay is running, a
handover zone will behave as another entry delay zone with a delay time as defined at P511E to
P526E. If an entry delay zone has not been activated and there is no entry delay running, a
handover zone becomes an instant zone with no entry delay. The Handover zone MUST have an
entry delay programmed.
P469E 1-8E Two Trigger Zones - Where options 1-8 represent zones 9-16 respectively. A zone defined as
two trigger at this address will only cause an activation if one of the following conditions are met;
a The zone is triggered twice within the two trigger time period as defined by Address P534E,
P535E or P536E
b Any two zones defined as two trigger activate once each within the two trigger time period as
defined by Address P534E, P535E or P536E
c A zone defined as two trigger is left violated for longer than the two trigger time period as
defined by Address P534E, P535E or P536E
P470E 1-8E Zone is 24 Hour - Where options 1-8 represent zones 9-16 respectively. 24 hour zones will
activate whether the panel or area is armed or disarmed. If an entry delay is also assigned to a
24hr zone, the alarm will not trigger unless the zone is in alarm longer than the delay time
programmed. (Default none)
P471E 1-8E Zone is 24 Hour Fire Zone - Where options 1-8 represent zones 9-16. 24 hour Fire zones will
activate whether the panel or area is armed or disarmed. If an entry delay is also assigned to a
24 hr Fire zone, the alarm will not trigger unless the zone is in alarm longer than the delay time
programmed. A Fire Zone will cause the output to pulse to differentiate it from a burglar alarm.
(Default none)
P472E 1-8E Zone is 24 Hour Auto-Reset - Where options 1-8 represent zones 9-16. 24 hour Auto-Reset
zones will activate whether the panel or area is armed or disarmed. If an entry delay is also
assigned to a 24 hr Auto-Reset zone, the alarm will not trigger unless the zone is in alarm longer
than the delay time programmed. An Auto-reset zone will seal automatically when the zone input
is restored back to normal i.e. does not require a code to reset an alarm. (Default none)
P473E 1-8E Day Zones - Where options 1-8 represent zones 9-16 respectively. Day zones are active during
periods where the panel or areas are disarmed and revert to normal zones during armed periods
(Default none)
P474E 1-8E Continuous Day Zone - Where options 1-8 represent zones 9-16 respectively. The zone acts as
a day zone at all times (Armed and Disarmed) and will operate day alarms but not normal zone
alarms (Default none)
P475E 1-8E Siren Lockout Zones - Where options 1-8 represent zones 9-16 respectively. Zones with siren
lockout designation will only cause their assigned outputs to operate once per armed period. Led
on = zone locked out. (Default none)