2.5 Accepting and Clearing Alarms
The operation of alarms in terms of how they are cleared is dependent upon the alarm type and also
the conguration option, which can be changed via Portables Pro 2.0.
The options are ‘latched’ and ‘non-latching’ and the functionality is described in the table below.
i
Alarm 2 cannot be congured and behaves as a latched alarm.
Conguration
Setting
(Alarm 1 only)
Instantaneous Alarm 1 Instantaneous Alarm 2
Latched
An instantaneous alarm 1
can be
cancelled by pressing the operator
button but only when the gas level has
dropped below the alarm level
An instantaneous alarm 2 can be
cancelled by pressing the operator
button but only when the gas level has
dropped below the alarm level
Non-latching
An instantaneous alarm 1
will not
be latched and will return to a non-
alarm state without user acceptance
once the gas level has dropped below
the alarm level
An instantaneous alarm 2 can be
cancelled by pressing the operator
button but only when the gas level has
dropped below the alarm level
i
While in alarm, T4 will continue to record levels of all the gases being monitored.