10 | Configuration
Installer reference guide
106
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
Malfunctioning
Room
Operation
User profile
Main zone
10.5.2 Room
Setpoint screen
Control the room temperature of the main zone via setpoint screen [1] Room.
See "10.3.5Setpoint screen"[495].
Schedule
Indicate if the room temperature is controlled according to a schedule or not.
# Code Description
[1.1] N/A Schedule:
▪ No: Room temperature is directly controlled by
the user.
▪ Yes: Room temperature is controlled by a
schedule and can be modified by the user.
Heating schedule
Applicable for all models.
Define a heating schedule of the room temperature in [1.2] Heating schedule .
See "10.3.7Schedule screen: Example"[496].
Cooling schedule
Only applicable if EKHVCONV2 is installed.
Define a cooling schedule of the room temperature in [1.3] Cooling schedule.
See "10.3.7Schedule screen: Example"[496].
Antifrost
Room frost protection [1.4] prevents the room from getting too cold. This setting
behaves differently depending on the set unit control method [2.9]. Perform
actions according to the table below.
Main zone unit control method [2.9] Description
Leaving water temperature control
([C‑07]=0)
Room frost protection is NOT guaranteed.
External room thermostat control
([C‑07]=1)
Allow for the external room thermostat to
take care of room frost protection:
▪ Set [C.2] Space heating/
cooling=On.
Room thermostat control
([C‑07]=2)
Allow for the user interface used as room
thermostat to take care of room frost
protection:
▪ Set antifrost [1.4.1] Activation=Yes.
▪ Set the temperature of the antifrost
function in [1.4.2] Room setpoint.