10 | Configuration
Installer reference guide
109
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
Room sensor offset
Only applicable in room thermostat control.
To calibrate the (external) room temperature sensor, give an offset to the value of
the room thermistor as measured by the user interface used as room thermostat
or by the external room sensor. The setting can be used to compensate for
situations where the user interface used as room thermostat or the external room
sensor cannot be installed at the ideal location.
See "6.6Setting up an external temperature sensor"[443]).
# Code Description
[1.6] [2-0A] Room sensor offset (user interface used as
room thermostat): Offset on the actual room
temperature measured by the user interface
used as room thermostat.
▪ –5°C~5°C, step 0.5°C
[1.7] [2-09] Room sensor offset (external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
▪ –5°C~5°C, step 0.5°C
10.5.3 Main zone
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone.
See "10.3.5Setpoint screen"[495].
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.
▪ In Weather dependent LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.
# Code Description
[2.1] N/A Schedule:
▪ 0: No
▪ 1: Yes
Heating schedule
Define a heating temperature schedule for the main zone via [2.2] Heating
schedule.
See "10.3.7Schedule screen: Example"[496].
Cooling schedule
Define a cooling temperature schedule for the main zone via [2.3] Cooling
schedule.
See "10.3.7Schedule screen: Example"[496].