10 | Configuration
Installer reference guide
90
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
6 Press the left dial to confirm the new setting.
7 Press the center button to go back to the home screen.
INFORMATION
When you change the overview settings and you go back to the home screen, the
user interface will show a popup screen and request to restart the system.
When confirmed, the system will restart and recent changes will be applied.
10.2 Configuration wizard
After first power ON of the system, the user interface will guide you using the
configuration wizard. This way you can set the most important initial settings. This
way the unit will be able to run properly. Afterwards, more detailed settings can be
done via the menu structure if required.
You can find a short overview of the settings in the configuration here. All the
settings can also be adjusted in the settings menu (use the breadcrumbs).
For the setting… Refer to…
Language [7.1]
Time/date [7.2]
Hours —
Minutes
Year
Month
Day
System
Indoor unit type (read only) "10.5.9Installer settings"[4137]
Backup heater type [9.3.1]
Domestic hot water [9.2.1]
Emergency [9.5.1]
Number of zones [4.4] "10.5.5Space heating/
cooling"[4123]
Backup heater
Voltage [9.3.2] "Backup heater"[4138]
Configuration [9.3.3]
Capacity step 1 [9.3.4]
Additional capacity step 2
[9.3.5] (if applicable)
Main zone