11 | Commissioning
Installer reference guide
159
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
6 During manual operation:
You can change the pump speed.
You must change the circuit.
To change these settings during the air purge, open the menu
and go to [A.3.1.5]: Settings.
Scroll to Circuit and set it to Space/Tank.
Scroll to Pump speed and set it to Low/High.
7 To stop the air purge manually:
1 Open the menu and go to Stop air purge.
2 Select OK to confirm.
INFORMATION
When air purging in automatic mode, the first air purge is always for the main zone,
the second started air purge is always for the additional zone. To air purge the
domestic hot water tank circuit, choose [A.3.1.5.2] Circuit=Tank at the start of
the manual air purge of the main zone or additional zone.
To perform an automatic air purge
INFORMATION
When purging the main zone, make sure the setpoint for the main zone is at least
5°C higher than the actual water temperature inside the unit.
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Room, Space heating/cooling and Tank operation.
1 Set the user permission level to Installer. See "To change
the user permission level"[488].
2 Go to [A.3]: Commissioning > Air purge.
3 In the menu, set Type = Automatic.
4 Select Start air purge.
5 Select OK to confirm.
Result: The air purge starts. It stops automatically when done.
6 To stop the air purge manually:
1 In the menu, go to Stop air purge.
2 Select OK to confirm.
11.4.3 To perform an operation test run
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Room, Space heating/cooling and Tank operation.
INFORMATION
The test run only applies to the additional temperature zone.

Table of Contents