10 | Configuration
Installer reference guide
111
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
# Code Description
[2.5] [1-00]
[1-01]
[1-02]
[1-03]
Set weather-dependent heating in [2.5] Heating
WD curve:
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
T
t
Target leaving water temperature (main zone)
T
a
Outdoor temperature
Set weather-dependent heating in [9.l]
Overview field settings:
▪ [1-00]: Low outdoor ambient temperature. –
40°C~+5°C
▪ [1-01]: High outdoor ambient temperature.
10°C~25°C
▪ [1-02]: Desired leaving water temperature
when the outdoor temperature equals or drops
below the low ambient temperature.
[9‑01]°C~[9‑00]°C
Note: This value should be higher than [1‑03]
as for low outdoor temperatures warmer water
is required.
▪ [1-03]: Desired leaving water temperature
when the outdoor temperature equals or rises
above the high ambient temperature.
[9‑01]°C~min(45, [9‑00])°C
Note: This value should be lower than [1‑02] as
for high outdoor temperatures less warm water
is required.
Cooling WD curve
Set weather-dependent cooling for the main zone (if [2.4]=2):