10 | Configuration
Installer reference guide
115
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
# Code Description
[2.8.3] [9-03] Cooling minimum:
5°C~18°C
[2.8.4] [9-02] Cooling maximum:
18°C~22°C
Control
Define how the operation of the unit is controlled.
Control In this control...
Leaving water Unit operation is decided based on the leaving water
temperature regardless the actual room temperature
and/or heating or cooling demand of the room.
External room
thermostat
Unit operation is decided by the external thermostat or
equivalent (e.g. heat pump convector).
Room thermostat Unit operation is decided based on the ambient
temperature of the user interface used as a room
thermostat.
# Code Description
[2.9] [C‑07] 0: Leaving water
1: External room thermostat
2: Room thermostat
Thermostat type
Only applicable in external room thermostat control.
Following combinations are possible to control the unit (not applicable when
[C‑07]=0):
[C‑07]=2 (Room thermostat)
a b c
a User interface at indoor unit
b User interface used as room thermostat at main zone
c External room thermostat at additional zone
[C‑07]=1 (External room thermostat)
a b c
a User interface at indoor unit
b External room thermostat at main zone
c External room thermostat at additional zone