10 | Configuration
Installer reference guide
142
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
# Code Description
[9.6.4] [8-02] Anti-recycle timer: Minimum time
between two cycles for domestic hot water. The
actual anti-recycling time also depends on setting
[8-04].
Range: 0~10 hours
Remark: The minimum time is 0.5 hours even
when the selected value is 0.
[9.6.5] [8-00] Minimum running timer:
Do NOT change.
[9.6.6] [8-01] Maximum running timer for domestic hot
water operation. Domestic hot water heating
stops even when the target domestic hot water
temperature is NOT reached. The actual
maximum running time also depends on setting
[8-04].
When Control=Room thermostat: This
preset value is only taken into account if there
is a request for space heating or cooling. If
there is NO request for space heating/cooling,
the tank is heated until the setpoint has been
reached.
When ControlRoom thermostat: This
preset value is always taken into account.
Range: 5~95 minutes
Remark: It is NOT allowed to set [8‑01] to a value
below 10 minutes.
[9.6.7] [8-04] Additional timer: Additional running time
for the maximum running time depending on the
outdoor temperature [4-02] or [F-01].
Range: 0~95 minutes
Water pipe freeze prevention
Only relevant for installations with water piping outdoors. This function tries to
protect outdoor water piping from freezing.
# Code Description
[9.7] [4-04] Water pipe freeze prevention:
0: Continuous pump operation (read
only)
NOTICE
Water pipe freeze prevention. Even if you turn OFF space heating/cooling operation
([C.2]: Operation > Space heating/cooling), water pipe freeze prevention –if
enabled– will remain active.