EasyManua.ls Logo

Daikin Altherma 3 H F - Page 205

Daikin Altherma 3 H F
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3/10
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Installer setting at variance with
default value
Field settings table
Additional zone
3.7 [2-0D] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
3.8.1 [9-05] R/W 15~37°C, step: 1°C
25°C
3.8.2 [9-06] R/W [2-0D]=2:
37~60, step: 1°C
55°C
[2-0D]2:
37~55, step: 1°C
55°C
3.8.3 [9-07] R/W 5~18°C, step: 1°C
8°C
(
*3
)
3.8.4 [9-08] R/W 18~22°C, step: 1°C
22°C
(
*3
)
Additional zone
3.A [C-06] R/W 0: -
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1 [1-0C] R/W 3~10°C, step: 1°C
5°C
3.B.2 [1-0E] R/W 3~10°C, step: 1°C
5°C
(
*3
)
Space heating / cooling
└─ Operation range
4.3.1 [4-02] R/W 14~35°C, step: 1°C
35°C
4.3.2 [F-01] R/W 10~35°C, step: 1°C
20°C
(
*3
)
Space heating / cooling
4.4 [7-02] R/W 0: 1 LWT zone
1: 2 LWT zones
4.5 [F-0D] R/W 0: Continuous
1: Sample
2: Re
q
uest
4.6 [E-02] R/W (*3)
R/O
0: Reversible (*3)
1: Heatin
g
onl
y
└─ Pump speed limitation
4.8.1 [9-0E] R/W 0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6
4.8.2 [9-0D] R/W 0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6
Space heating / cooling
4.9 [F-00] R/W
0: Restricted
1: Allowed
4.A [D-03] R/W 0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, s
p
an 8°C
4.B [9-04] R/W 1~4°C, step: 1°C
1°C
4.C [2-06] R/W 0: Disabled
1: Enabled
Tank
5.2 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
5.3 [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
5.4 [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
5.6 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
└─ Disinfection
5.7.1 [2-01] R/W 0: No
1: Yes
5.7.2 [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunda
y
5.7.3 [2-02] R/W 0~23 hour, step: 1 hour
1
5.7.4 [2-03] R/W
60°C
5.7.5 [2-04] R/W 40~60 min, step: 5 min
40 min
Tank
5.8 [6-0E] R/W 40~60°C, step: 1°C
60°C
5.9 [6-00] R/W 2~40°C, step: 1°C
28°C (*4)
22°C
(
*5
)
5.A [6-08] R/W
2~20°C, step: 1°C
10°C
5.B R/W
0: Fixed
1: Weather de
p
endent
└─ WD curve
Cooling minimum
Cooling maximum
Delta T cooling
Space cooling OFF temp
Operation day
Number of zones
Antifrost
Duration
Tank setpoint
Hysteresis
Hysteresis
Start time
Setpoint mode
Maximum
Heat up mode
Reheat setpoint
Eco setpoint
Comfort setpoint
Delta T heating
Additional zone
Emitter type
Heating minimum
Heating maximum
Space heating OFF temp
Thermostat type
Main zone
Pump operation mode
Unit type
Pump outside range
Increase around 0°C
Overshoot
Activation
(*1) *6V_(*2) *9W_
(*3) + EKHVCONV2_
(*4) EAVZ16S18*_(*5) EAVZ16S23*
(#) Setting is not applicable for this unit. 4P556077-1A - 2021.02

Table of Contents