EasyManua.ls Logo

Daikin Altherma 3 H F - Page 32

Daikin Altherma 3 H F
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 | Application guidelines
Installer reference guide
32
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
C Room 2
D Main leaving water temperature zone
E Room 3
a Outdoor unit
b Indoor unit
c Heat exchanger
d Backup heater
e Motorised 3-way valve (mixing the main zone)
f Additional pump
g Main pump
h Shut-off valve
i Collector (field supply)
j Remote controller of the heat pump convectors (field supply)
k User interface used as room thermostat
HPC1...3 Heat pump convectors (field supply)
FHL1...3 Floor heating loops (field supply)
For the main zone: the room temperature is controlled by the user interface,
which is used as room thermostat (optional equipment EKRUDAS).
For the additional zone:
- The external thermostat is directly connected to the indoor unit.
- The desired room temperature is set via the external thermostat and the
thermostatic valves of the radiators in each room.
- The heating demand signal from the external thermostat is connected to the
digital input on the indoor unit (X2M/35a and X2M/30). The indoor unit will
only supply the desired additional leaving water temperature when there is an
actual demand.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the user interface.
Note:
Main room = user interface used as
room thermostat functionality
Other rooms = external room
thermostat functionality
Number of water temperature zones:
#: [4.4]
Code: [7-02]
1 (Dual zone): Main + additional
In case of heatpump convectors:
External room thermostat for the
additional zone:
#: [3.A]
Code: [C-06]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition.
Shut-off valve output Set to follow the thermo demand of the
main zone.
Benefits
Comfort. The smart room thermostat functionality can decrease or increase the
desired leaving water temperature based on the actual room temperature
(modulation).

Table of Contents