www.DaikinApplied.com 31 CAT 258 • REBEL APPLIED ROOFTOP
A. Semi-custom packaged rooftop air conditioners
A. AFBMA 9 - Load ratings and fatigue life for ball
bearings.
B. AMCA 99 - Standards handbook.
C. AMCA 210 - Laboratory methods of testing fans for
rating purposes.
D. AMCA 300 - Test code for sound rating air moving
devices.
E. AMCA 500 - Test methods for louver, dampers, and
shutters.
F. AHRI Standard 340/360- Unitary large equipment
G. AHRI Standard 920 - DOAS
H. AHRI Standard 1060 - Rating air-to-air heat
exchangers for energy recovery ventilation
equipment
I. ASTM B117 - Standard practice for operating salt
spray apparatus.
J. NEMA MG1 - Motors and generators.
K. NFPA 70 - National Electrical Code.
L. UL 723 - Test for surface burning characteristics of
building materials.
M. UL 900 - Test performance of air lter units.
N. UL 1995 - Standard for heating and cooling
equipment.
O. UL 94 - Test for ammability of plastic materials for
parts in devices and appliances.
P. IBC 2000, 2003 - International Building Code.
Q. NFPA 90A - Standard for the installation of air
conditioning and ventilating systems.
R. NFPA 5000 - Building construction and safety code.
S. ASHRAE 90.1 Energy Code.
T. ASHRAE Std. 111 - Measurement, testing, adjusting,
and balancing of building hvac systems
A. Shop drawings: Indicate assembly, unit dimensions,
weight loading, required clearances, construction
details, eld connection details, electrical
characteristics and connection requirements.
B. Product data:
1. Provide literature that indicates dimensions,
weights, capacities, ratings, and electrical
characteristics and connection requirements.
2. Provide data on lter media, lter performance,
lter assembly, and lter frames.
3. Provide computer generated fan curves with
specied operating point clearly plotted.
C. Manufacturers must clearly dene any exceptions
made to plans and specications. Any deviations in
layout, arrangement, or eciency shall be submitted
to the consulting engineer prior to bid date.
Acceptance of deviation (s) from specications shall
be in the form of written approval from the consulting
engineer.
A. Maintenance data: provide instructions for
installation, maintenance and service
A. Manufacturer: company specializing in
manufacturing the products specied in this section
with minimum ve years documented experience,
who issues complete catalog data on total product.
B. Certify packaged rooftop performance in accordance
with AHRI 340/360 standards
C. Product energy eciency compliant with ASHRAE
90.1 minimum energy eciency requirements
D. Startup must be done by trained personnel
experienced with rooftop equipment.
E. Do not operate units for any purpose, temporary
or permanent, until ductwork is clean, lters and
remote controls are in place, bearings lubricated,
and manufacturers’ installation instructions have
been followed.
A. Deliver, store, protect and handle products to site.
B. Handle carefully to avoid damage to components,
enclosures, and nish
C. Store in a clean, dry place to protect from weather
and construction trac.