EasyManua.ls Logo

Daikin EBSX-D - Page 18

Daikin EBSX-D
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Piping installation
Installation manual
18
EBSH/X(B)11+16P50D
Daikin Altherma 3 R ECHO
4P759878-1 – 2024.01
2 Connect the shut-off valves using the flat gaskets (accessory
bag) to the space heating/cooling water pipes of the indoor unit.
3 Connect the space heating/cooling field piping to the shut-off
valves using a sealing.
Do NOT exceed the maximum tightening torque (Thread size 1",
25-30 N•m). To avoid damage, apply the necessary countertorque
with a suitable tool.
2
≤Ø7 mm
1
3
4 Connect the domestic hot water in and out pipes to the indoor
unit.
Do NOT exceed the maximum tightening torque (Thread size 1",
25-30 N•m). To avoid damage, apply the necessary countertorque
with a suitable tool.
1
2
5 Support the water piping.
For rearward facing connections: Support hydraulic lines suitably
according to the spatial conditions. This is valid for all water pipes.
dc
b a
a Space heating/cooling water OUT (screw connection, 1")
b Space heating/cooling water IN (screw connection, 1")
c Domestic hot water OUT (screw connection, 1")
d Domestic cold water IN (cold water supply)(screw
connection, 1")
NOTICE
It is recommended to install shut-off valves on the
space heating/cooling water in and out connections, as
well as on the domestic cold water in and domestic hot
water out connections. These shut-off valves are field
supplied.
However, make sure there is no valve between the
pressure relief valve (field supply) and the DHW
tank.
NOTICE
Install air purge valves at all local high points.
NOTICE
A pressure relief valve (field supply) with an opening
pressure of maximum 10 bar (=1 MPa) must be installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

Table of Contents

Related product manuals