IM 1059-12 LARGE VERTICAL WSHP 8 www.DaikinApplied.com
installation Considerations
Table 1: Sheave adjustment settings
Unit Size
Motor
HP
Motor Shaft
Diameter
Motor
RPM
0 Turns 1 Turn 2 Turns 2.5 Turns 3 Turns 4 Turns 5 Turns 6 Turns
072
1.5 0.625 1750 770 735 700 683 665 630 595
2.0 0.875 1750 1329 1264 1231 1199 1134 1069 1005
3.0 1.125 1765 1340 1275 1242 1209 1144 1079 1013
096
1.5 0.625 1750 960 903 847 819 790 734 677
2.0 0.875 1750 1329 1264 1231 1199 1134 1069 1005
3.0 1.125 1765 1406 1346 1316 1286 1227 1167 1107
120
2.0 0.875 1750 1242 1185 1129 1101 1073 1016 960
3.0 1.125 1765 1340 1275 1242 1209 1144 1079 1013
5.0 1.125 1750 1394 1335 1305 1275 1216 1157 1097
180
3.0 1.125 1765 1108 1070 1051 1033 995 958 920
5.0 1.125 1750 1307 1263 1241 1218 1174 1130 1085
7.5 1.375 1750 1462 1418 1373 1351 1329 1285 1241 1196
215
3.0 1.125 1765 1001 967 950 933 899 866 832
5.0 1.125 1750 1160 1121 1101 1081 1042 1003 963
7.5 1.375 1750 1462 1418 1373 1351 1329 1285 1241 1196
290
7.5 1.375 1750 1229 1191 1154 1136 1117 1080 1043 1005
10.0 1.375 1765 1407 1360 1336 1312 1264 1216 1169
Note: Bold numbers denote factory setting