EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
Si20-701_B Troubleshooting by Remote Controller
96
3.8
A6
Fan Motor (M1F) Lock,
Overload
Remote Controller Display
A6
Applicable Models
FMCQ, FMDQ
Method of Error Detection
Detection by failure of signal for detecting number of
turns to come from the fan motor
Error Decision Conditions
When number of turns can not be detected even when
output voltage to the fan is maximum
Supposed Causes
îš„ Fan motor lock
îš„ Disconnected or defective wiring between fan motor
and PCB

Table of Contents